For full functionality of this site it is necessary to enable JavaScript.

Chauvin Arnoux C.A 6030 Electrical Installation Tester

- Voltage / frequency : measurement automatic upon connection to installation: from 2 to 550 V (DC or RMS) / from 15.3 to 450 Hz
- Differential test: 
+ I∆n = 10 – 30 – 100 – 300 - 500 mA - Adjustable : 6mA to 650 mA
+ non-tripping test: at ½ I∆n
+ tripping time measurement: at I∆n, 2 I∆n, 5 I∆n, 150 mA, 250 mA
+ tripping current / time measurements:ramp from 0.5...1.06 I∆n, in 3% increments
+ fault voltage: 5.0 to 50.0 V by calculation I∆n x RE- short-circuit current: displayed up to 40 kA by calculation IK = UREF / ZL-PE
- Earth loop / live earth:
+ by RCD test without tripping and without tripping using 1 auxiliary rod: from 0.1 to 4000Ω
+ calculation of fault voltage and short-circuit current 
- Current measurement: using clamp connections 20 A (MN20 & C172) or 200 A (C174)
- Phase rotation order: on installation frequencies from 15.3 to 64 Hz and voltage 90 to 550 V using conventional method (3 wires) or sequential method (2 wires) 
- General specifications
+ Power supply: 6 x 1.5 V batteries or rechargeable batteries complies with standards EN 61010-1 and EN 61557, Electromagnetic compatibility (EMC) rating EN 61326 
+ IP 54     
+ Dimensions: 211 x 108 x 60 mm / 900 g

Thiết bị tiêu chuẩn: Supplied with "hands free" carrying strap and accessories bag:
1 mains lead
1 3-wire lead
3 test probes / 3 crocodile clips
1 user's manual in 5 languages
1 data transfer application software
1 communication lead

Details

datasheet
user guider

Description

Innovative and particularly user-friendly, the C.A 6030 RCD is particularly easy to use and offers high metrological performance for the testing protection systems and installations' compliance with the European and international standards NF C 15-100, VDE 0100, NIN/NIV, IEEE 16th, ÖVE EN-1.

  • Direct, safe connection to installation mains socket
  • Reliable measurements due to automatic permutation of L and N inputs if conductors are reversed at socket connection
  • Automatic installation voltage and frequency measurement
  • Tests standard, selective, A and AC RCDs
  • 5 fixed ranges 10/30/100/300/500 mA + 1 adjustable range from 6 to 650 mA
  • RCD non-trip test / trip time measurement (pulse or ramp mode) and exact trip current (ramp mode)
  • Power-on earth measurement: earth loop and 1P earth
  • Current and leakage current measurement with clamp (option)
  • Phase rotation test (2 or 3-wire)
  • Cat.III 600 V
  • Programmable alarms, date-stamped recording of measurement readings, data printout using standard printer, direct transfer of data to PC (transfer software included as standard)
  • Large backlit display / "hands-free" bag
  • Battery-powered - battery life: 2,000 tests
  • Dimensions: 270 x 250 x 60 mm; weight: 900 g
  • Quality Engagement
  • Easy change and return
  • Delivery Avaliable
  • Favorable payment

Apply your mail to get promotion information