HV HIPOT GDKC-13A High Voltage Circuit Breaker Analyzer
Manufacturer: HV HIPOT Model: GDKC-13A Origin: China Guarantee: 12 Month - Request a Quotation
- Contact
Usage Environment
- Input Power: 220V±10%, 50Hz±10%
- Air Pressure: 86-106kpa
- Temperature: -10-40℃
- Humidity: ≤80%RH
Safety Performance
- Insulation Resistance>2MΩ
- Dielectric Strength: Shell can withstand power frequency voltage 1.5kV at 1 minute without flash-over and arcing.
The Basic Parameters
a. Time:
Range 4000.0+6000.0 ms
Resolution 0.1ms
Error 0.1ms ± 1digit within 100ms
0.1% ± 1digit more than 100ms Same period
b. Velocity
Range: 20.00m/s; resolution: 0.01m/s
Error: ± 0.1m/s ± 1digit within 0-2m/s ± 0.2m/s±1digit more than 100ms
c. Range
Vacuum breaker: Range: 50.0mm; Resolution: 0.1mm; Error: 0.1±1mm
SF6 circuit breaker: Range: 300.0mm; Resolution: 1mm; Error: 0.1±1mm
Oil circuit breaker: Range: 600.0mm; Resolution: 1mm; Error: 0.1±1mm
d. Current: range 20.00A; resolution 0.01A
r. Output power: DC25-250V digital adjustable / 20A(instantaneous working), resolution 1V.
f. Dimensions: 360mm (L)* 280mm (W)* 300mm (H)
g. Weight: 9kg
- Quality Engagement
- Easy change and return
- Delivery Avaliable
- Favorable payment