Schloeder CWG 1528 Coupling network Surge (240 VAC, 120VDC, 6A)

Nominal voltage AC: max. 240 V, 50/ 60 Hz

Nominal voltage DC: max. 120 V

Nominal /max. current: 4 x 6 A at 40° C ambient temperature

Decoupling inductance: 4 x 20 mH / 6 A (Serial choke)

Coupling capacity: 0,5 µF and 40 ohm

Max. surge pulse: 1,2/50 µs 4400 V

High voltage surge input: Fischer high voltage jack D105A039

EUT feeding: laboratory-banana-jacks

EUT connection: laboratory-banana-jacks

Remote: serial, RS 232

Power supply: electronic control system IEC-plug 230 V / 50 Hz / 1 A on rear side

Additional earth connection: jacks on front and rear side

Temperature environment: 0 - 40 °C

Rel. humidity: 0 – 60%

Cabinet: 19" housing, 3 HE

Weight app.14Kg