Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Input voltage range: 180 to 264 Vac: 2400 W; 90 to 140 Vac: 1400 W
Frequency: 47 Hz to 63 Hz
Max input current 11.5 Arms at 100/200 Vac
Main DC Output
Nominal setting: MIN: 12.175 /NOM: 12.2/ MAX: 12.225
Total output regulation range: MIN: 11.6 V/ MAX: 12.9 V
Output current: MIN: 8.0 A (minimum starting load for a 20% transient step)/ MAX: 196.7 A at high line; 114.75 A at low line
Standby DC Output
Nominal setting: MIN: 11.95/ NOM: 12/ MAX: 12.05
Total output regulation range: MIN: 11.4 V/ MAX: 12.6 V
Output current: MIN: 0.0 A/ MAX: 3.5 A
Operating temperature:
Forward air: 0 to 50 °C, allowable up to 60 °C at 1800 W
Reverse air: 0 to 40 °C, allowable up to 50 °C at 1700 W
Operating relative humidity: Up to 95% non-condensing
Nominal Main Output: 12.2 V @ TBD
Standby Output: 12 V @ 3.5 A
Airflow Direction: Reverse