Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Gases and sensors: GfG transmitters for combustible, oxygen and toxic gases and vapors
GMA 200-MW wall mounting (dimensions): Approx. 8.23 x 7 x 2.52 in / 209 x 180 x 64 mm (W x H x D)
Display and control elements: Backlit LCD graphical display 1.3 x 2 in (33 x 53 mm with 132 x 65 pixels); 5 buttons (left, right, up, down, OK); LED indicators: 8 status and alarm (4x red, 1x green, 3x yellow); 6 relay (6x red)
Connection options: Gas warning system GMA 200–MW4: Up to 4 analog or digital detectors
Inputs: 4 analog inputs (4–20 mA or 0.2–1 mA); max. 50 Ohm input resistance; 2 digital inputs: Acknowledgement of alarms can be freely configured; 2x RS485 BUS (for connection of external relay modules or digital transmitters in BUS wiring); 1x RS485 BUS (for digital transfer of measured and output data to a higher-level control center or with master functionality of a GMA 200-MW for the connection of GMA 200-RT relay modules)
Outputs: Modbus (RS485); 4 relays (normally open contact), freely configurable for single alarms per measuring point and alarm threshold, configuration of collective or group alarms, fault messages and voting functions; 1 relay for maintenance and 1 for fault messages (closed-circuit principle); 2 analog outputs: 4–20 mA / 600 Ohm max. resistance, freely configurable
Alarms: 3 independent threshold alarms per measuring point (AL1, AL2, AL3); Gas alarms can be freely set in the measuring range
Alarm activation logic: Ascending, descending, exceeding, not achieved acknowledgeable (additional horn only), non-acknowledgeable, non-self-locking / self-locking
Data storage: Measured values stored on 2 GB microSD card; Intervals can be set (5 sec.–60 min.); Records instantaneous and mean values, minimum/maximum concentration; Logger settings individually programmable per measuring channel
Ambient temperature: Operation: -4 °F to +125 °F / -20 °C to +50 °C; Storage: -22 °F to +140 °F / -30 °C to +60 °C
External relay module: 16 relays per module; up to 4 relay modules per GMA 200-MW4 system (for up to 64 additional relays); freely configurable for single alarms per measuring point and alarm threshold, configuration of collective or group alarms, fault messages and voting functions
Power supply: 2 x 24 V DC, 20–30 V (1 x redundant voltage supply)
Power consumption: GMA 200–MW4 Controller: 30 W (incl. connected detectors); Relay module GMA 200 RT: 6 W