HV HIPOT GDTF(L)-2160/60 AC Resonant Test System For Generators (0-60kV; 2160kVA)
Manufacturer: HV HIPOT Model: GDTF(L)-2160/60 Origin: China Guarantee: 12 Month - Contact
Rated output voltage: 0 ~ 50kV (RMS) or below.
Output frequency: 45 - 300Hz.
Waveform: pure sine wave, THD ≤ 1%.
Max. capacity: 2000kVA or below.
Duty cycle: continuous working 15mins one time at full power output.
Quality factor: 10 - 40.
Frequency adjustment sensitivity: 0.1HZ, instability of <0.05%.
Power supply: 220V or 380V ± 15%, 50HZ ± 5%.
Input voltage (V): 380
Output voltage (kV): 0-60
Capacity (kVA): 2160
Application scope: Generator--capacitance to the ground 0.5-2.5 μF
Main configurations:
60kV/9A Fixed reactor 2 sets
60kV/9A Adjustable reactor 2 sets
Capacitive divider 60kV
- Quality Engagement
- Easy change and return
- Delivery Avaliable
- Favorable payment