For full functionality of this site it is necessary to enable JavaScript.
EMIN.COM.MM
0
Product image

MEGGER MIT430/2 CAT IV Insulation Testers (1000 V)

ModelMIT430/2
P/N1004-740
Contact
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Insulation:

Test voltage

Nominal: 50 V, 100 V, 250 V, 500 V, 1000 V

Insulation accuracy

50 Volts. 10 GΩ ± 2% ± 2 digits ± 4.0% per GΩ

100 Volts. 20 GΩ ± 2% ± 2 digits ± 2.0% per GΩ

250 Volts. 50 GΩ ± 2% ± 2 digits ± 0.8% per GΩ

500 Volts. 100 GΩ ± 2% ± 2 digits ± 0.4% per GΩ

1000 Volts 200 GΩ ± 2% ± 2 digits ± 0.2% per GΩ

Service Error: BS EN 61557-2 (2007).

50V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.5%

100V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3%

250V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3%

500V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3%

1000V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 11.5%

Display range Analogue: 1 GΩ full scale

Resolution: 0.1 kΩ

Short circuit/charge current: 2 mA +0% -50% to EN 61557-2 (2007)

Open circuit voltage insulation: -0% +2% ± 2V

Test current: 1 mA at min. pass value of insulation to a maximum of 2 mA max.

Leakage (not MIT400/2): 10% ±3 digits

Voltage: 3% ±3 digits ±0.5% of rated voltage

Timer control (not MIT400/2): 60 second countdown timer

Note: Above specifications only apply when high quality silicone leads are being used.

Continuity:

Continuity measurement: 0.01 Ω to 1000 kΩ

Continuity accuracy:

± 3% ± 2 digits (0 to 100 Ω )

±5% ±2 digits (100 to 500kΩ) (500kΩ to 1MΩ unspecified)

Service Error: BS EN 61557-4 (2007) - ± 2.0%, 0.1 Ω - 2 Ω ± 6.8%

Open circuit voltage: 5 V ± 1 V

Test current: 200 mA (–0 mA +20 mA) (0.01 Ω to 4 Ω)

Polarity (not MIT400/2): Single polarity (Default) / Dual polarity (configurable on setup).

Lead resistance: Null up to 9.00 Ω

Voltage:

Display range

AC: 0.0 mV to 600 V

DC: 0.0 mV to 600 V

Volt range accuracy:

DC: ±2% ±2 digits.

AC: ±2% ±2 digits (not specified for > 100 Hz) (10 mV to <10 V TRMS

Sinusoidal, 15 Hz to 100 Hz)

AC: ±2% ±2 digits (>10 V TRMS Sinusoidal, 15 Hz to 400 Hz)

Service Error: BS EN 61557-1 (2007) ±10 % ±2 digits

Waveform:

Non-sinusoidal (15 Hz to 400 Hz): ±3% ± 2 digits >100 mV to

600 V TRMS

±8% ± 2 digits 10 mV to 100 mV TRMS


Frequency disply range: 15 Hz – 400 Hz (20 mV to 600 V)

Frequency measurement accuracy: ±0.5% ±1 digits (15 Hz to 99.9 Hz).

Capacitance measurement: 1 nF to 10 μF

Capacitance measurement accuracy: ± 5.0% ± 2 digits (0.1 nF – 1 nF unspecified)

Storage:

Storage capacity: >1000 test results

Data download:

Bluetooth® wireless

Bluetooth® Class II

Range: up to 10 m

Power supply: 6 x 1.5 V cells type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) Alkaline 6 x 1.2 V NiMH rechargeable cells may be used

Battery life: 3000 insulation tests with duty cycle of 5 sec ON /55 sec OFF @ 1000 V into 1 MΩ

Charger (Optional): 12-15 V DC (accessory interface)

Dimensions Instrument 228 mm x 108 mm x 63 mm (9.00 in x 4.25 in x 2.32 in)

Weight 600 g

Datasheet

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.

Quick Support

Direct access to our certified experts