MEGGER MIT430/2 CAT IV Insulation Testers (1000 V)
Insulation:
Test voltage
Nominal: 50 V, 100 V, 250 V, 500 V, 1000 V
Insulation accuracy
50 Volts. 10 GΩ ± 2% ± 2 digits ± 4.0% per GΩ
100 Volts. 20 GΩ ± 2% ± 2 digits ± 2.0% per GΩ
250 Volts. 50 GΩ ± 2% ± 2 digits ± 0.8% per GΩ
500 Volts. 100 GΩ ± 2% ± 2 digits ± 0.4% per GΩ
1000 Volts 200 GΩ ± 2% ± 2 digits ± 0.2% per GΩ
Service Error: BS EN 61557-2 (2007).
50V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.5%
100V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3%
250V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3%
500V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3%
1000V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 11.5%
Display range Analogue: 1 GΩ full scale
Resolution: 0.1 kΩ
Short circuit/charge current: 2 mA +0% -50% to EN 61557-2 (2007)
Open circuit voltage insulation: -0% +2% ± 2V
Test current: 1 mA at min. pass value of insulation to a maximum of 2 mA max.
Leakage (not MIT400/2): 10% ±3 digits
Voltage: 3% ±3 digits ±0.5% of rated voltage
Timer control (not MIT400/2): 60 second countdown timer
Note: Above specifications only apply when high quality silicone leads are being used.
Continuity:
Continuity measurement: 0.01 Ω to 1000 kΩ
Continuity accuracy:
± 3% ± 2 digits (0 to 100 Ω )
±5% ±2 digits (100 to 500kΩ) (500kΩ to 1MΩ unspecified)
Service Error: BS EN 61557-4 (2007) - ± 2.0%, 0.1 Ω - 2 Ω ± 6.8%
Open circuit voltage: 5 V ± 1 V
Test current: 200 mA (–0 mA +20 mA) (0.01 Ω to 4 Ω)
Polarity (not MIT400/2): Single polarity (Default) / Dual polarity (configurable on setup).
Lead resistance: Null up to 9.00 Ω
Voltage:
Display range
AC: 0.0 mV to 600 V
DC: 0.0 mV to 600 V
Volt range accuracy:
DC: ±2% ±2 digits.
AC: ±2% ±2 digits (not specified for > 100 Hz) (10 mV to <10 V TRMS
Sinusoidal, 15 Hz to 100 Hz)
AC: ±2% ±2 digits (>10 V TRMS Sinusoidal, 15 Hz to 400 Hz)
Service Error: BS EN 61557-1 (2007) ±10 % ±2 digits
Waveform:
Non-sinusoidal (15 Hz to 400 Hz): ±3% ± 2 digits >100 mV to
600 V TRMS
±8% ± 2 digits 10 mV to 100 mV TRMS
Frequency disply range: 15 Hz – 400 Hz (20 mV to 600 V)
Frequency measurement accuracy: ±0.5% ±1 digits (15 Hz to 99.9 Hz).
Capacitance measurement: 1 nF to 10 μF
Capacitance measurement accuracy: ± 5.0% ± 2 digits (0.1 nF – 1 nF unspecified)
Storage:
Storage capacity: >1000 test results
Data download:
Bluetooth® wireless
Bluetooth® Class II
Range: up to 10 m
Power supply: 6 x 1.5 V cells type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) Alkaline 6 x 1.2 V NiMH rechargeable cells may be used
Battery life: 3000 insulation tests with duty cycle of 5 sec ON /55 sec OFF @ 1000 V into 1 MΩ
Charger (Optional): 12-15 V DC (accessory interface)
Dimensions Instrument 228 mm x 108 mm x 63 mm (9.00 in x 4.25 in x 2.32 in)
Weight 600 g
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts