Operating: voltage range: ±20% of nominal
Frequency: 60 Hz
CT input: 0-0.5 VAC operating, 3 VAC maximum
Connectors: UL, CSA recognized, detachable screw terminals (14 AWG), 600V
Operating temp range: -30 to 60°C (-22 to 140°F)
Operating humidity range: 0 to 90% RH, non-condensing
Dimensions: 8.5 cm x 14.3 cm x 3.8 cm (3.3 in. x 5.6 in. x 1.5 in.)
Weight: 295 g (10.4 oz.)
Number of data channels: 2
Delta or Wye configuration ranges: 480 Volts AC
3 Phase 3 Wire(No neutral)
3 Phase 4 Wire
Accuracy: ±0.45% of reading + 0.05% FS through 25th harmonic (dependent on CT used and line variation accuracy could be 1.5% to 4% of reading)
Provides accurate measurement at a low cost to meet your needs for sub-metering, net-metering, energy management, and performance contracting applications. This WattNode Delta or Wye-connection kWh Transducer works with Magnelab AC Current Transformers and a Pulse Input Adapter to provide True RMS kilowatt hours of energy used, even for loads with non-sinusoidal waveforms. Because these sensors tie directly into the line, they should only be used by qualified personnel. This model supports a 3-phase Delta-connection of 480 VAC.