Tested object: CT Burden, PT Burden
Measure item:
CT Burden: Resistance (R), Inductance (X)
PT Burden: Conductance (g), Susceptance (b)
Power supply: AC 220V 50Hz
Rated capacity: ~500VA
Rated current of CT Burden: 1A, 2A, 5A
Rated voltage of PT Burden: 100V, 100/√3V, 100/3V, 110V, 110/√3V, 110/3V, 120V, 120/√3V, 120/3V, 200V, 150V, 220V, 165V, 180V, 240V
Accuracy class: ±1%
Testing range:
Resistance (R): 0 - 199.9 Ω
Inductance (X): 0 - 199.9 Ω
Conductance (g): 0 - 199.9 mS
Susceptance (b): 0 - 199.9 mS
Minimum resolution:
Resistance (R): 0.0001 Ω
Inductance (X): 0.0001 Ω
Conductance (g): 0.0001 mS
Susceptance (b): 0.0001 mS
Measure model of CT Burden: 4-terminal measure
Measure model of PT Burden: 2-terminal measure
Display model: 7'' LCD
Operation model: Touch screen
Operating system: English version
Communication function: Provided the RS232 communication interface
Dimension (~): 460mm x 380mm x 160mm
Weight (~): ~32kg