Measureable conductor size: Max. φ110mm
Measuring range: AC 0 to 1000Arms(1850Apeak)
Output voltage: AC 0 to 500 mVrms (0.5 mV/A)
Accuracy (sine wave input): + Band width: ±0.8% rdg ±0.2 mV(45 to 65 Hz) ±1.5% rdg ±0.4 mV(40 to 1 kHz)
+ Phase: ±2.0° or less (45Hz to 65 Hz) ±3.0° or less (40Hz to 1 kHz)
Temperature & humidity range (guaranteed accuracy): 23 ±5°C, 85%RH or less(no ondensation)
Current consumption (at power supply 3V): 2 mA max. (at power supply ±5 V)
Rated voltage between circuit and ground: AC 600 Vrms max
Operating temperature & humidity range: 0 to 50°C, 85% RH or less (no ondensation)
Storage temperature & humidity range: -20 to 60°C, 90% RH or less (no ondensation)
Temperature coefficient: 0.03% rdg./°C (-10 to 50°C)
Maximum allowable input: AC 1300 Arms
Influence of the conductor location: Within ±1.5%rdg
Influence of the external magnetic field: Current that flows through the conductor ±2.0% rdg or less when separated by a distance of D/4 (37.5 mm) from the conductor
Output impedance: 100Ω or less
Withstand voltage: AC5.4kVrms / 5 seconds Between circuit and sensor.
Recommended calibration period: 1 year
Environmental condition: Altitude up to 2000 m, in-door use
Dimension: 24(W) × 65(H) × 22(D)mm (excluding projections)
Cable length Clamp sensor – circuit box: approx. 2.7m Circuit box – output terminal: approx. 0.2m
Output terminal: MINI DIN 6PIN
Weight: Approx.170g
Accessory: Instruction manual, Cable marker