1. Power supply:AC 220V,50HZ;
2. Total power:2KW;
3. Timer: timing accuracy < 1s/h;
4. Heat flux measurement range: (0-15) Kw / m2;
5. Heat flux meter accuracy: ± 0.2Kw / m2;
6. Heat flux meter accuracy: <± 3%;
7. Thermal radiation temperature measurement range: 400-600 ℃, accuracy ± 0.5 ℃;
8. Blackbody temperature error: ± 5 ℃;
9. Exhaust speed: (2.5 ± 0.2) m / s;
10. Exhaust capacity: (39-85) m3 / min;
11. Porous refractory radiant panel size: 300mm × 450mm, about 900 ℃ high temperature capability;
12. Thermocouple: K diameter stainless steel sheathed thermocouple of 3.2mm;
13. Heat flux distribution requirements: at 200mm : (9.1 ± 0.4) KW / m2;
at 400mm : (5.0 ± 0.4) KW / m2;
at 600mm : (2.4 ± 0.2) KW / m2;
14. Combustion gases: propane (Customer);
15. Combustion gas flow rate: (0.026 ± 0.002) L / S;
16. Combustion burner: outer diameter ¢ 10mm inner diameter ¢ 6mm, burner tube hit 35 ¢ 0.7mm hole;
17. Flame height: 60 ~ 120mm adjustable;
18. Ignition system: high-voltage electronic ignition;
19. Powerful exhaust system: This machine is equipped with a powerful exhaust fan, when the test is completed, the system will start the exhaust fan exhaust outside.