Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

Power Supply
Host: DC9V, alkaline dry battery LR6X 1.5VX6PCS;
Detector: DC9V alkaline dry battery 6LR61, 9V
Phase Detecting Mode
1. Contact mode phase detecting:Power line below 35KV
2.Non-Contact mode phase detecting: thepower line voltage exceeds35kV, must adopt non-contact mode to testing
Phase Detecting Voltage: 220V~220kV
Phase Detecting Distance: 60 meters
Phase Qualitative: In phase:-25°~25°;out phase: 95°~145°and 215°~265°
Range
Test phase:0.0°~360.0°
Test frequency: 45.0Hz~65.0Hz
Accuracy: phase detecting:≤±12°
frequency:≤±2Hz
Resolution: phase :0.1° frequency:0.1Hz
Transmitting Frequency: 433MHz、315MHz
Phase Indication: Vector graphics and numbers are displayed at the same time
Power Indication: The detector has a green power indicator
Work Indication: The phase detecting time detector has a sound and light indication function, a red double flashing light indication and a ”beep-beep-beep" beep.
Display Rate: 2 times/second
Memory: 9999 groups (no data will be lost if the battery is powered down or replaced)
LCD Backlight: Adjustable brightness, adapt to different environments
Automatic Shutdown: The meter will automatically turn off after about 15 minutes of power-on
Battery Voltage: When the battery voltage drops to 7.2V±0.1V, the low battery voltage symbol is displayed to remind the battery to be replaced. At this time, the measured data is also accurate.
Rated Current: Detector: 30mA max; host: 150mA max
Instrument Size: Host: about 195mm×100mm×45mm; detector: about 290mm×250mm×80mm
Instrument Weight: Receiver: About 500g (including battery); detector: about 257g×2 (including battery); total mass: about 6.85kg (including accessories)
Length Of Telescopic Insulating Rod: 4300mm
Insulation Test: After the insulating rod is stretched, both ends: AC 220kV/rms host, detector: AC3700V/rms (between exposed metal and plastic shell)
External Interference: No extra-strong electromagnetic field; no 433MHz co-frequency interference
Protection Level: IP63
Suitable Safety Standard
GB13398-92, GB311.1-311.6-8, 3DL408-91 standards and the newly promulgated national power industry standard "General Technical conditions for 1kV~35kV Portable Nuclear phase Shifters for Live Operation DL/T 971-2017" requirements
Comply with IEC61481-A2; 2004; IEC 61243-1 ed.2:2003 standard
Working Temperature & Humidity: -10℃~40℃; below 80%RH
Store Temperature & Humidity: -10℃~60℃; below 70%RH