Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Calibration: carbon monoxide CO
Sensor type: electrochemical
Sampling method: Diffusion
Detection range: 0...300 ppm CO
0...1000 ppm CO
Resolution: 1 ppm CO
Repeatability: < ± 5%
Sensor lifetime: > 10 years
Power supply: 12...36 VDC (default), 24 VAC or 230 VAC as options
Digital interface: RS485, Modbus RTU protocol
Analog outputs: 2 × 4-20 mA / 0-10 V, user settable
Output relays: 2 × SPST relays (closing contact)
250 VAC / 30 VDC, 5 A max
Default alarm set-points: 25 ppm / 35 ppm CO
Enclosure: grey ABS plastic, wall mount, IP65
Dimensions: H85 × W82 × D55 mm
Operating conditions: -20...+50 °C, 15...90% RH