Measurement time, programmable: 4...1024 cycles
Fastest response time (at 50Hz): 85...165 ms
Energy metering: max. 32 meters
Individual harmonics and THD V/I: via Modbus interface
Auto-scaling V/I inputs: supported
Inputs: via screw terminals 6 mm2
Nominal current: adjustable 1...5 A
Maximum: 7.5 A (sinusoidal)
Consumption: ≤ I2 x 0.01 Ω per phase
Overload capability:
10 A continuous
100 A, 10 x 1 s, interval 100 s
Nominal voltage: 57.7…400 VLN, 100...693 VLL
Maximum: 480 VLN, 832 VLL (sinusoidal)
Consumption: ≤ U2 / 1.54 MΩ per phase
Impedance: 1.54 MΩ per phase
Overload capability:
480 VLN, 832 VLL continuous
600 VLN, 1040 VLL, 10 x 10 s, interval 10 s
800 VLN, 1386 VLL, 10 x 1 s, interval 10 s
Nominal frequency: 45… 50 / 60 …65 Hz
Measurement TRMS: up to 31st harmonic
Types Of Connection: Single phase, 3/4-wire balanced load (3U,1I)
Power Supply: via screw terminals 6 mm2
Nominal voltage: 100…230 V AC ±15%, 50...400 Hz
24...230 V DC ±15%
Consumption: ≤ 10 VA
Analog Outputs: 4 analog outputs, bipolar ±20mA
Bus connection: RS-485 (Modbus/RTU protocol)
Protection rating: IP30 (housing), IP20 (terminals)
Overvoltage category: CAT III up to 600V
Dimensions (H x B x D): 110 x 70 x 70mm
Weight: 500 g