Time measurement: 12 natural switching (closing) time
The opening (closing) phase is not at the same time
The difference between different periods of switching (closing)
Closing (opening) Bouncing time (number of bounces)
Internal trigger test range: 1ms ~ 10000ms, resolution: 0.01ms,
External trigger test range: 1ms ~ 10000ms,
Resolution within 999ms: 0.01ms,1000-9999ms: 0.1ms, and over 10000ms: 1ms.
Accuracy within 200ms: 0.05%± 0.1ms
Velocity measurement: instant separating (instant closing) velocity
Appointed time slot( stroke segment or angle segment) average velocity
Speed measurement range: 0.1mm sensor 0.01~20.00m/s
345°angle sensor 1 cycle/ 0.01°
Travel measurement: Travel of moving contact (travel)
Contact stroke (open distance)
Over travel
Overshoot or rebound stroke
Measuring range: linear sensor: 50mm, measuring range: 0-50mm, resolution :0.1mm.
Optional 100-1000mm linear sensor of any length.
Encoder: 345° Rotate sensor, measurement
range: 0-1000mm, resolution :0.1о.
Current resistance range: the maximum current 30 A, resolution: 0.01 A, 1000 Ω resistance, resolution: 0.01 Ω.
Instrument power supply: AC 220V ± 10%; 50 hz plus or minus 10%
Dc power output: continuously adjustable DC20 ~ 270V, DC220V≤20A (short time), Power: 4400W.
External trigger voltage: AC/DC10-300V, current ≤120A
Disconnecting switch measurement range: Voltage output DC20~270V(adjustable)
Current output time: 0.01~10 s (settable)
Fracture signal maximum acquisition time: 10s
Measurable fracture closing, separation time, three-phase a synchronism , bounce time and frequency .
Mainframe volume: 360×260×170mm
Operating environment: -20℃~+50℃
Relative humidity: ≤90%