Order code: 701155/8-01-0253-2001-23- 044-005/059
Measuring range:
RTD temperature probe: -200 to +850 °C
Thermocouples: -200 to 2495 °C
Version: Default setting
National language: German (default setting)
Switching behavior: Safety temperature limiter max. alarm (opening function)
Measurement input1 (programmable): 2x Pt100 in three-wire circuit (default setting)
Voltage supply: AC 110 to 240 V +10 % /-15 %, 48 to 63 Hz
Ignition protection type: [Ex ia] associated apparatus, installation outside the Ex-area
Analog output (configurable): 4 to 20 mA (default setting)
Extra code: SIL, PL, IPL approval is always present
The device is primarily built to monitor thermotechnical processes accurately and switch the systems to a safe operating status in the event of malfunctions. As a result, risks to people, the environment, production facilities, and production goods can be identified and averted at an early stage