Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

No alarm output A3,A4
Power supply
Supply voltage : 24 V DC, ± 15 %
: < 5 VA
Operating temperature : -10..+55 °C
CE-conformity : EN 61326-1:2013; EN 60664-1:2007
Input
Fault function : break of wire (RTD Pt100/1000, Thermocouple) and short-circuit (only Pt100/1000)
RTD : Pt100 (3-wire) -100.0..+600.0 °C
Pt1000 (3-wire) -100.0..+300.0 °C
: Thermocouple (TC)
type J -100.0..+800.0 °C
type K -150..+1200 °C
type N -150..+1200 °C
type S -50..+1600 °C
cold junction compensation integrated
Accuracy : <0.1 %, ±1 Digit
Display : Graphic LCD-Display, 128 x 64 Pixel, with white back-lite
Output
Alarm A1-A4 : relay SPDT
< 250 V AC < 250 VA < 2 A
cos Phi ≥ 0.3
< 300 V DC < 40 W <2 A
Analog output: 0/4..20 mA, 0/2..10 V DC, isolated
- Accuracy : 0.2 %;TK 0.01 %/K
Fault indication : for broken line or short circuit detection
→ analog output (programmable)
0 mA, < 3.6 mA or >21.5 mA
→ Alarm relays
min. or max. function programmable
Case : Polyamide (PA) 6.6 , UL94V-0
TS35 acc. to DIN EN 60715:2001-09
Weight : approx. 450 g
Connection : screw terminals 0.14..2.5 mm²
AWG 26..AWG14
Protection class : case IP30, terminals IP20 acc. to BGV A3